Parker Hannifin Corporation
Parflex Division
Ravenna, Ohio
Bulletin No. 4660-PGP2T
Parflex
®
Flexible Gas Piping System
Design and Installation Guide
Section 7.0 Sizing Tables
7.1 CSST Tables
Natural Gas
Caution: Locate proper sizing table based on total pressure drop allowed in piping system by local utility for each
installation.
*Table includes losses for four 90 degree bends and two end fittings. To determine flow capacity for tubing runs with additional bends
and/or fittings, add the appropriate number of feet to the actual run length using the formula: L = 1.3n. L = number of feet to be added to
actual run length; n = number of additional bends and/or fittings.
Table 1*
Maximum Flow Capacity of Parker Parflex Tubing in Cubic Feet per Hour
Gas Pressure: 0.5 psi or less; Pressure Drop: 0.5 in. WC
(Based on a 0.60 Specific Gravity Gas)
Part
Tube
Tubing Length (ft.)
No.
Size
5
10
15
20
25
30
40
50
60
70
80
90
100 125 150 200 250 300 350 400 450 500
PGP-6
3/8”
49
35
28
25
22
20
17
16
14
13
12
12
11
10
9
8
7
6
6
5
5
4
PGP-8
1/2”
119
87
72
64
57
53
47
42
39
36
34
32
31
28
26
23
20
19
18
17
16
15
PGP-12
3/4”
228 163 134 117 105
96
84
75
69
64
60
57
54
49
44
39
35
32
30
28
26
25
PGP-16
1”
601 422 343 297 265 241 208 186 169 157 146 138 130 116 106
92
82
75
69
64
61
57
PGP-20 1-1/4”
1037 746 615 536 482 442 386 347 318 295 277 262 249 224 205 179 161 148 137 129 122 116
PGP-32
2"
3181 2274 1869 1626 1459 1336 1162 1043 955 886 831 785 746 669 613 533 479 438 407 381 360 342
Table 2*
Maximum Flow Capacity of Parker Parflex Tubing in Cubic Feet per Hour
Gas Pressure: 0.5 psi or less; Pressure Drop: 1.0 in. WC
(Based on a 0.60 Specific Gravity Gas)
Part
Tube
Tubing Length (ft.)
No.
Size
5
10
15
20
25
30
40
50
60
70
80
90
100 125 150 200 250 300 350 400 450 500
PGP-6
3/8”
66
48
40
35
32
29
26
24
22
20
19
18
17
16
15
13
12
11
11
10
10
9
PGP-8
1/2”
162 117
97
85
77
71
63
58
53
50
48
46
44
40
38
34
32
30
29
27
27
26
PGP-12
3/4”
326 233 191 166 149 137 119 107
98
91
85
80
76
68
63
54
49
45
41
39
37
35
PGP-16
1”
860 604 491 424 379 345 298 266 242 224 209 197 187 167 152 131 117 107
99
92
87
82
PGP-20 1-1/4”
1442 1037 885 746 671 615 536 482 442 411 386 364 347 312 286 249 224 205 191 179 169 161
PGP-32
2"
4449 3181 2614 2274 2041 1869 1626 1459 1336 1240 1162 1098 1043 936 857 746 669 613 569 533 504 479
Table 3*
Maximum Flow Capacity of Parker Parflex Tubing in Cubic Feet per Hour
Gas Pressure: 0.5 psi or less; Pressure Drop: 1.5 in. WC
(Based on a 0.60 Specific Gravity Gas)
Part
Tube
Tubing Length (ft.)
No.
Size
5
10
15
20
25
30
40
50
60
70
80
90
100 125 150 200 250 300 350 400 450 500
PGP-6
3/8”
86
61
52
45
42
38
34
30
28
26
24
23
22
20
18
16
14
13
12
11
11
10
PGP-8
1/2”
205 147 122 106
97
89
79
74
67
64
62
57
57
52
50
45
44
41
40
37
37
36
PGP-12
3/4”
424 303 248 215 193 178 154 139 127 118 110 103
98
90
82
69
63
58
52
50
48
45
PGP-16
1”
1119 786 639 551 493 449 388 346 315 291 272 256 244 218 198 170 152 139 129 120 113 107
PGP-20 1-1/4”
1749 1258 1037 904 813 746 650 585 536 498 468 442 420 378 347 302 272 249 232 217 205 195
PGP-32
2"
5413 3870 3181 2767 2484 2274 1978 1776 1626 1509 1414 1336 1270 1140 1043 908 815 746 692 649 613 582