CC-LINK Network Communication
WUME-SCHG1C-4
4-5
4-3 Memory map
4-3-1 CC-Link mode 1
■
Remote input RX (Mode 1 communication unit → Master station)
This is a read-only register for input from the communication unit to the master station in units of
bits.
Values cannot be written to this register.
Before using mode 1, be sure to configure the “page” settings.
For details, refer to
<Remote input RX>
RX
F
E
D
C
B
A
9
8
7
6
5
4
3
2
1
0
+00
Sensor response data switching response
Not used
Command
response
Not used Error
code Not used Command
Sensor
head
value
Calcu-
lated
value
Normal
mea-
sured
value
Judg-
ment
value
Error
flag
Send
response
+10
Not used
Page
Page 3 Page 2 Page 1
+20
Not used
Judgment output 1 (OUT1)
Slave
unit 14
Slave
unit 13
Slave
unit 12
Slave
unit 11
Slave
unit 10
Slave
unit 9
Slave
unit 8
Slave
unit 7
Slave
unit 6
Slave
unit 5
Slave
unit 4
Slave
unit 3
Slave
unit 2
Slave
unit 1
Master
unit
+30
Not used
Judgment output 2 (OUT2)
Slave
unit 14
Slave
unit 13
Slave
unit 12
Slave
unit 11
Slave
unit 10
Slave
unit 9
Slave
unit 8
Slave
unit 7
Slave
unit 6
Slave
unit 5
Slave
unit 4
Slave
unit 3
Slave
unit 2
Slave
unit 1
Master
unit
+40
Not used
Judgment output 3 (OUT3)
Slave
unit 14
Slave
unit 13
Slave
unit 12
Slave
unit 11
Slave
unit 10
Slave
unit 9
Slave
unit 8
Slave
unit 7
Slave
unit 6
Slave
unit 5
Slave
unit 4
Slave
unit 3
Slave
unit 2
Slave
unit 1
Master
unit
+50
Not used
Alarm output
Slave
unit 14
Slave
unit 13
Slave
unit 12
Slave
unit 11
Slave
unit 10
Slave
unit 9
Slave
unit 8
Slave
unit 7
Slave
unit 6
Slave
unit 5
Slave
unit 4
Slave
unit 3
Slave
unit 2
Slave
unit 1
Master
unit
+60
Error output
Commu-
nication
unit
Slave
unit 14
Slave
unit 13
Slave
unit 12
Slave
unit 11
Slave
unit 10
Slave
unit 9
Slave
unit 8
Slave
unit 7
Slave
unit 6
Slave
unit 5
Slave
unit 4
Slave
unit 3
Slave
unit 2
Slave
unit 1
Master
unit
+70
Not used
Remote
ready
Error
state
Setting
initializa-
tion done
Initial-
ization
request
Not used
<Setting details>
Name
Device No.
Description
Command response
Send response
RX[00]
RY[00]: Response bit to a send request.
This bit is set when transmission of a command to a controller is completed.
Error flag
RX[01]
This bit is set when the command response from a controller is an error.
Sensor response data switching response (*1)(*2)
Judgment value
(*3)
RX[08]
RY[08]: Response bit to a judgment value.
This bit is set when judgment value mode is entered.
Normal mea-
sured value (*3) RX[09]
RY[09]: Response bit to a normal measured value.
This bit is set when normal measured value mode is entered.
Calculated value
(*3)
RX[0A]
RY[0A]: Response bit to a calculated value.
This bit is set when calculated value mode is entered.
Sensor head
value (*3)
RX[0B]
RY[0B]: Response bit to a sensor head value.
This bit is set when sensor head value mode is entered.
Command
RX[0C]
RY[0C]: Response bit to a command.
This bit is set when command mode is entered.
Error code
RX[0E]
RY[0E]: Response bit to an error code.
This bit is set when error mode is entered.
Содержание SC-HG1-C
Страница 2: ...WUME SCHG1C 4 2 MEMO ...
Страница 8: ...WUME SCHG1C 4 8 MEMO ...
Страница 16: ...WUME SCHG1C 4 1 8 MEMO ...
Страница 17: ...2 1 2 System Configuration 2 1 Communication unit system 2 2 2 2 Unit types 2 4 ...
Страница 22: ...WUME SCHG1C 4 2 6 MEMO ...
Страница 106: ...WUME SCHG1C 4 4 72 MEMO ...
Страница 107: ...5 1 5 Specifications 5 1 Specifications 5 2 5 2 Dimensions 5 3 ...
Страница 110: ...WUME SCHG1C 4 5 4 MEMO ...
Страница 111: ...6 1 6 Warranty 6 1 When you purchase and use the product 6 2 ...
Страница 114: ...WUME SCHG1C 4 6 4 MEMO ...
Страница 115: ...7 1 7 Maintenance 7 1 Maintenance and Inspection 7 2 7 1 1 Maintenance cautions 7 2 7 1 2 Main inspection items 7 2 ...
Страница 124: ...WUME SCHG1C 4 8 8 MEMO ...
Страница 125: ...Revision History 1st edition 1 27 2017 2nd edition 9 8 2017 3rd edition 9 30 2019 4th edition 12 1 2019 ...
Страница 126: ... MEMO ...
Страница 127: ... MEMO ...