Troubleshooting
WUME-SCHG1C-4
8-4
<Table of error codes>
The following table shows error codes and corrective actions.
Error code
Description
Action
DEC
HEX
100
0x0064 A command was received that is not in the com-
mand list.
The command code is invalid. Check “4-10
Commands” for the correct code.
101
0x0065 An out-of-range setting parameter was re-
quested.
Invalid setting parameter.
Check the settable parameter values in
102
0x0066 A write request using an unusable setting
was made in the target controller.
Invalid setting parameter.
Check the settable parameter values in
103
0x0067 A read request using an unusable setting
was made in the target controller.
Invalid setting parameter.
Check the settable parameter values in
200
0x00C8 A sensor head is not connected.
Check the status of the sensor head con-
nection.
400
0x0190
When calibration was executed, an alarm,
undefined, or over display range state was in
effect.
Invalid sensor head value. Check the state
of the sensor head.
401
0x0191 Calibration was not executed normally.
Calibration failed.
For the calibration procedure, refer to the
user’s manual of the controller that you use.
500
0x01F4
When teaching was executed, an alarm, un-
defined, or over display range state was in
effect.
Invalid sensor head value. Check the state
of the sensor head.
501
0x01F5 Unable to execute teaching.
Teaching failed.
For the teaching procedure, refer to the
user’s manual of the controller that you use.
600
0x0258
When preset was executed, an alarm, un-
defined, or over display range state was in
effect.
Invalid sensor head value. Check the state
of the sensor head.
700
0x02BC When bank load or bank save was executed,
the bank number was outside the range.
Invalid setting parameter.
Check the settable parameter values in
800
0x0320 Unable to write to internal memory.
The controller may have failed. Replace the
controller.
900
0x0384
A response was not received from the con-
troller for 100ms after the command request
was sent.
Check the status of the controller connection.
1900
0x0076C
A normal command was not sent.
Abnormal measured value block information.
The communication unit process timed out.
Check the status of the communication unit
connection.
2200
0x0898 A request was made to a controller / slave
unit that is not connected.
A command request was made to a control-
ler / slave unit that does not exist.
Check the command request controller.
2400
0x0960 A command request was received while re-
covering from a horizontal connection error.
A command was requested while recovering
from an error. Wait until controller process-
ing finishes before requesting a command.
2500
0x09C4
2600
0x0A28 The controller is busy.
Another command was requested while the
controller was busy. Wait until controller pro-
cessing finishes before requesting a com-
mand.
2800
0x0AF0 A CRC error occurred during communication
between controllers
Noise may have caused the CRC error to
occur. Check the wiring.
2900
0x0B54 A timeout error occurred during communica-
tion between controllers
Check the status of the controller connection.
Содержание SC-HG1-C
Страница 2: ...WUME SCHG1C 4 2 MEMO ...
Страница 8: ...WUME SCHG1C 4 8 MEMO ...
Страница 16: ...WUME SCHG1C 4 1 8 MEMO ...
Страница 17: ...2 1 2 System Configuration 2 1 Communication unit system 2 2 2 2 Unit types 2 4 ...
Страница 22: ...WUME SCHG1C 4 2 6 MEMO ...
Страница 106: ...WUME SCHG1C 4 4 72 MEMO ...
Страница 107: ...5 1 5 Specifications 5 1 Specifications 5 2 5 2 Dimensions 5 3 ...
Страница 110: ...WUME SCHG1C 4 5 4 MEMO ...
Страница 111: ...6 1 6 Warranty 6 1 When you purchase and use the product 6 2 ...
Страница 114: ...WUME SCHG1C 4 6 4 MEMO ...
Страница 115: ...7 1 7 Maintenance 7 1 Maintenance and Inspection 7 2 7 1 1 Maintenance cautions 7 2 7 1 2 Main inspection items 7 2 ...
Страница 124: ...WUME SCHG1C 4 8 8 MEMO ...
Страница 125: ...Revision History 1st edition 1 27 2017 2nd edition 9 8 2017 3rd edition 9 30 2019 4th edition 12 1 2019 ...
Страница 126: ... MEMO ...
Страница 127: ... MEMO ...