7-8
The operations for each setting when a communication error occurs are described below.
1) I/O operation : halt
- System register No. 28: 0 (Halt operation)
Note) System register No. 27: 0 or 1, Undefined Mode selector switch SW1/SW7: ON or OFF,
Undefined
[Operation]
- All I/O operation: Halt
- "COMM. LED(COM. LED)" on the normal master station and slave station: Flashing (at normal speed,
0.2-second cycle)
- Output state of all slave stations: OFF
[Step to take]
Turn off the power supply to the master station. Replace the faulty unit with a normal unit and power up
again.
2) I/O operation : Continue
- System register No. 28: 1 (Continue operation)
- Mode selector switch SW1/7: OFF (Halt operation)
Note) System register No. 27: 0 or 1, Undefined
When teh system register No. 27 is 0, it is OK to set the mode selector switch SW7 to ON.
[Operation]
I/O operation of the remote I/O and I/O units on the master station: Continue
I/O operation of normal I/O units and normal advanced units on a slave station system: Continue
[Step to take]
Turn off the power supply to the CPU. Replace the faulty unit with a normal unit and power up again.
3) I/O operation : Continue [2] (automatic reset)
- System register No. 28: 1 (Continue operation)
- System register No. 27: 1 (Continue operation)
- Mode selector switch SW1/7: ON (Continue operation)
[Operation]
I/O operation of the remote I/O and I/O units on the master station: Continue
I/O operation of normal I/O units and normal advanced units on a slave station system: Continue
[Step to take]
Power up the slave station system which has had a unit replaced and it automatically resets.
However, since the "ERROR LED" on the CPU remains on, the initialize switch on the CPU must be set
to be on in the RUN mode.
Reference:
Set the operation mode when an error occurs using the system registers and the mode selector switches
as below.
[Example]
When a communication error occurs, only the remote I/O control will stop.If a slave station is outputting
data when the error occurs, the status will be maintained.If an error occurs in a unit on the slave station
syste, the operation will be continued.
[Setting]
- System register No. 27: 1
- System register No. 28: 1
- Mode selector switch SW1/7 on Master unit: OFF
- Mode selector switch SW3 on Slave unit: ON
Содержание MEWNET-F
Страница 9: ...Chapter 1 Functions and Restrictions of the Unit ...
Страница 19: ...Chapter 2 Part Names and Functions ...
Страница 40: ...2 22 ...
Страница 41: ...Chapter 3 Unit Specifications ...
Страница 52: ...3 12 ...
Страница 53: ...Chapter 4 Installation and Wiring ...
Страница 62: ...4 10 ...
Страница 63: ...Chapter 5 Connection for the Remote I O System ...
Страница 75: ...Chapter 6 Remote I O Map ...
Страница 84: ...6 10 ...
Страница 85: ...Chapter 7 Operation Modes for Controlling MEWNET F ...
Страница 97: ...Chapter 8 Control by MEWNET F ...
Страница 108: ...8 12 Flowchart ...
Страница 110: ...8 14 ...
Страница 111: ...Chapter 9 Troubleshooting ...
Страница 120: ...9 10 ...
Страница 121: ...9 11 9 5 2 When the ALARM LED is ON ...
Страница 122: ...9 12 9 5 3 When the Communication LED on the Master Unit does Not Flash Normally ...
Страница 123: ...9 13 When the COMM LED is OFF ...
Страница 124: ...9 14 When the COMM LED is ON ...
Страница 125: ...9 15 9 5 4 When the Communication LED on a Slave Station does Not Flash Normally ...
Страница 126: ...9 16 When the COMM LED is OFF ...
Страница 127: ...9 17 When the COMM LED is ON ...
Страница 128: ...9 18 9 5 5 When the CPU does Not Operate ...
Страница 129: ...9 19 9 5 6 When the Input Output Function of a Slave Station does Not Work ...
Страница 130: ...9 20 9 5 7 When the Memory Access Function for the Advanced Unit s Memory does Not Work ...
Страница 134: ...9 24 ...
Страница 135: ...Chapter 10 Dimensions ...
Страница 136: ...10 2 10 1 FP2 Multi wire Link Unit AFP2720 10 2 FP3 Remote I O Master Unit AFP3742 ...
Страница 137: ...10 3 10 3 FP2 Remote I OSlave Unit AFP2745 10 4 FP3 Remote I OSlave Unit AFP3745 ...
Страница 141: ...10 7 10 8 FP0 I O Link Unit AFP0732 ...
Страница 142: ...10 8 ...
Страница 143: ...Chapter 11 Appendix 1 I O Link With FP1 ...
Страница 147: ...11 5 11 3 Part Names and Functions ...
Страница 159: ...Chapter 12 Appendix 2 I O Link With FP0 ...
Страница 164: ...12 6 ...
Страница 165: ...Record of changes Manual No Date Desceiption of changes FAF 35E 1 Mar 2008 First edition ACG M0028 1 FAF 35 13 ...
Страница 166: ......
Страница 167: ......
Страница 168: ...FAF 35E 1 200803 http www mew co jp ac e fasys 2008 ...