9-3
9.2 Self-diagnostic Functions of MEWNET-F
When an error occurs when using [MEWNET-F], you can check the error with the self-diagnostic error
codes.
Procedure
FP programmer: Execute "OP-110".
FPWIN GR: Execute [STATUS DISPLAY].Error codes will be displayed on the screen.The description of
error codes are as below
9.2.1 Self-diagnostic Error Table
Error
code
Description
CPU
operation
Actions
35
An illegal unit is installed
on the slave station
Halt
An illegal unit is installed on the slave
staiton.Remove the illegal unit.
36
Remote I/O usage limit
Halt
Number of slots, number of I/O points exceeds
the limit.Use them within the limit.
37
Remote I/O map overlap
or range overflow error
Halt
Reset the I/O map so that the assignments do
not overlap.
38
FP I/O terminal board
registration error
Halt
Correctly set the registration value in the I/O map
for the FP I/O terminal board.
46
Remote I/O
communication error
Note1)
Selection
Note2)
A communication error (such as the
disconnection of communication path or the
power off of remote slave station) occurs.Fix the
source of the error.
For the details of the method to check a slave
station which has produced an error, refer to "14-
4. Checking a Slave Station Which Has Produced
an Error". (OP8 -> DT9131(DT90131) to
DT9137(DT90137)
47
I/O attribute error on the
slave station
Note1)
Selection
Note2)
Verification error or error in an advanced unit, etc
Perform a check of the I/O unit.
(OP8 -> DT9131(DT90131) to DT9137(DT90137)
51
Remote I/O terminal
station error
Run
The setting of the terminal station for remote I/O
is incorrect.Correctly set the terminal station
again.
52
Remote I/O update
synchronous error
Run
Please contact us.
Note1) You can check where the error has occurred by monitoring the special data register with a
programming tool.
FP programmer: Execute "OP-8".
FPWIN GR: Execute "STATUS DISPLAY" or "DATA MONITOR".
Note2) You can select whether the CPU will halt or not when an error occurs by setting a system register.
(0: Continue, 1: Stop)
[Remote I/O slave link error] System register No. 27
[I/O error in the remote I/O slave station] System register No. 28
Reference:
<Chapter 7 Operation Modes for Controlling MEWNET-F>
Содержание MEWNET-F
Страница 9: ...Chapter 1 Functions and Restrictions of the Unit ...
Страница 19: ...Chapter 2 Part Names and Functions ...
Страница 40: ...2 22 ...
Страница 41: ...Chapter 3 Unit Specifications ...
Страница 52: ...3 12 ...
Страница 53: ...Chapter 4 Installation and Wiring ...
Страница 62: ...4 10 ...
Страница 63: ...Chapter 5 Connection for the Remote I O System ...
Страница 75: ...Chapter 6 Remote I O Map ...
Страница 84: ...6 10 ...
Страница 85: ...Chapter 7 Operation Modes for Controlling MEWNET F ...
Страница 97: ...Chapter 8 Control by MEWNET F ...
Страница 108: ...8 12 Flowchart ...
Страница 110: ...8 14 ...
Страница 111: ...Chapter 9 Troubleshooting ...
Страница 120: ...9 10 ...
Страница 121: ...9 11 9 5 2 When the ALARM LED is ON ...
Страница 122: ...9 12 9 5 3 When the Communication LED on the Master Unit does Not Flash Normally ...
Страница 123: ...9 13 When the COMM LED is OFF ...
Страница 124: ...9 14 When the COMM LED is ON ...
Страница 125: ...9 15 9 5 4 When the Communication LED on a Slave Station does Not Flash Normally ...
Страница 126: ...9 16 When the COMM LED is OFF ...
Страница 127: ...9 17 When the COMM LED is ON ...
Страница 128: ...9 18 9 5 5 When the CPU does Not Operate ...
Страница 129: ...9 19 9 5 6 When the Input Output Function of a Slave Station does Not Work ...
Страница 130: ...9 20 9 5 7 When the Memory Access Function for the Advanced Unit s Memory does Not Work ...
Страница 134: ...9 24 ...
Страница 135: ...Chapter 10 Dimensions ...
Страница 136: ...10 2 10 1 FP2 Multi wire Link Unit AFP2720 10 2 FP3 Remote I O Master Unit AFP3742 ...
Страница 137: ...10 3 10 3 FP2 Remote I OSlave Unit AFP2745 10 4 FP3 Remote I OSlave Unit AFP3745 ...
Страница 141: ...10 7 10 8 FP0 I O Link Unit AFP0732 ...
Страница 142: ...10 8 ...
Страница 143: ...Chapter 11 Appendix 1 I O Link With FP1 ...
Страница 147: ...11 5 11 3 Part Names and Functions ...
Страница 159: ...Chapter 12 Appendix 2 I O Link With FP0 ...
Страница 164: ...12 6 ...
Страница 165: ...Record of changes Manual No Date Desceiption of changes FAF 35E 1 Mar 2008 First edition ACG M0028 1 FAF 35 13 ...
Страница 166: ......
Страница 167: ......
Страница 168: ...FAF 35E 1 200803 http www mew co jp ac e fasys 2008 ...