Connection of regenerative resistor
Size
Internal
regenerative
resistor
Connection of the Terminal
In case of using the external regenerative
resistor
In case of not using the external
regenerative resistor
H
None
Between P and B:
Connect the external regenerative resistor
Between RB and B : Keep open
* Connectors X1 to X7 are secondary side circuits. (See Page 11)
Insulation is required from the primary side power supply (power supply for motor brake).
Do not connect to the same power supply.
* Since the dynamic brake is not built in, it is in the free-run state when the motor emergency stops.
If it can cause a machine collision accident, please use the external dynamic brake resistor.
*The indication of built-in dynamic brake resistance is up to 3 times in succession due to maximum allowable inertia,
stop from rated speed.
If it is used under more conditions, the resistance may be broken and the dynamic brake may not operate.