No. SX-DSV03224-33-
R6.0
Motion Control Business Unit, Panasonic Corporation
7
.
Configuration of connectors and terminal blocks
7-1 Power connectors XA , XB , XC , XD and terminal blocks
Size A, B 100 V / 200 V
Pin No.
Symbol
Name
Description
XA
5
L1
Main power input
terminal
100 V
Single phase
100-120 V
+ 10 %
50/60 Hz
- 15 %
Use L1 and L3 terminal for single phase input
4
L2
200 V
Single or 3 phase
200-240 V
+ 10 %
50/60 Hz
- 15 %
3
L3
Use L1 and L3 terminal for single phase input
2
L1C
Control power
input terminal
100 V
Single phase
100-120 V
+ 10 %
50/60 Hz
- 15 %
1
L2C
200 V
Single phase
200-240 V
+ 10 %
50/60 Hz
- 15 %
XB
6
P
Regenerative
resistor connecting
terminal
To use an external regenerative resistor (customer prepared), connect an
external regenerative resistor between P and B.
In addition, parameter setting is required for the regenerative resistor. For
details, refer to "Technical Refarence - Functional Specification-"
Do not connect anything to the N terminal.
5
N
4
B
3
U
Motor output
terminal
Connect each phase of the motor winding.
U: U phase V: V phase W: W phase
When using Voice coil motor, connect the following.
U: U phase W: W phase
Do not connect anything to V terminal.
For details, refer to "Technical Reference - Function Specification-"
2
V
1
W
Earth
Earth terminal for grounding
*Tighten the Earth screw with a torque of M4: 1.0 to 1.2 N · m.