PB
MATE-Displayed FLEXmax 80 STATUS SETPT (SET POINT) Screen
Press the first two soft keys simultaneously
to return to the MAIN Menu.
CC SETP(OINT) Screens
•
Absorb:
displays the voltage that initiates and maintains the Absorb cycle
•
Float:
displays the voltage that begins the Float cycle and is maintained during this cycle
STATUS/CC/SETPT---------P00
Absorb 28.8 VDC
DOWN STATUS PORT
STATUS/CC/SETPT---------P00
Float 27.2 VDC
DOWN UP TOP PORT
STATUS/CC/METER------
end of setpoint
menu
UP TOP STATUS
g
MATE-Displayed FLEXmax 80 Advanced Screens
The FLEXmax 80 Advanced Screens displayed on the optional OutBack MATE include CHGR
(CHARGER), CCADV (ADVANCED), EQ, AND AUX. The
Advanced
screens allow the user to change various
values and set points.
MAIN------------------------------
12:00:30P
SUM STATUS SETUP ADV
ADV/SETTINGS/WARNING
changes made could adversely
effect system performance
ADV/PASSWORD-------------
enter the password
132
ENTER INC DEC EXIT
ADV/PASSWORD-------------
enter the password
141
ENTER INC DEC EXIT
ADV------------------------------
choose device:
FX CC DC MATE
ADV/CC/PAGE 1 ----------------
choose category:
ADV CHGR CCADV PG2
ADV/CC/CHGR--------------P01
output current 80.0A
limit
DOWN INC DEC PORT
ADV/CC/CHGR--------------P01
absorb voltage 14.4V
DOWN INC DEC PORT
g
g
g
g
g
ADV/CC/CHGR--------------P01
float voltage 13.6V
DOWN INC DEC PORT
ADV/CC/CHGR------------------
end of charger menu
TOP ADV MAIN
g
ADV------------------------------
choose device:
FX CC DC MATE
Содержание FLEXMAX 80
Страница 9: ...THE OUTBACK POWER SYSTEMS FLEXmax 80 Maximum Power Point Tracking Charge Controller...
Страница 13: ...12 Figure 2 Single Charge Controller wiring diagram with 24 volt PV array...
Страница 14: ...13 Figure 3 Charge Controller Wiring Diagram with an FX HUB 4 and an RTS...
Страница 15: ...14 Figure 4 Charge Controller with PV array ground fault protection wiring digram...
Страница 37: ...36 Figure 5 Diversion Load and AUX Wiring Set Up Illustrated...