PB
ADVANCED MENU
Absorb End Amps
00 A
EXIT NEXT - +
ADVANCED MENU
Rebulk Voltage
12.6 V
EXIT NEXT - +
An
Absorb
charge cycle normally ends when a battery
voltage is maintained at the
Absorb
set point for the user-
determined time period. Use the
< ->
or
< + >
soft keys to adjust the
Absorb End Amps
to an
optimal value (the default value is 00). While the battery
voltage is at or above the Absorb target and the
Absorb
End Amps
value is reached for a time delay of 15 seconds,
the FLEXmax 80 will switch to the Float stage regardless
of the charger time minutes as shown in the
Misc
menu
under
ChgT
. The charger timer will be cleared. This is an
optional set point and is used for few installations.
When finished with any adjustments, press the
<NEXT>
soft key to view the
Rebulk Voltage
screen.
In
Float,
if the battery voltage falls below the
ReBulk
Voltage
set point for at least 90 seconds, the FLEXmax
80 will automatically reinitiate a
Bulk
charge cycle. The
default is set to 6 volts, a very low value that will disable
this function. The
Rebulk Voltage
value can be adjusted by
pressing the
< - >
or
< + >
soft keys. Press the
<NEXT>
soft key to view the
Vbatt Calibration
screen.
Figure 6
NOTE: In
BULK
, the FLEXmax 80 will charge as long as necessary to complete the
cycle, regardless of the timer’s set points
Содержание FLEXMAX 80
Страница 9: ...THE OUTBACK POWER SYSTEMS FLEXmax 80 Maximum Power Point Tracking Charge Controller...
Страница 13: ...12 Figure 2 Single Charge Controller wiring diagram with 24 volt PV array...
Страница 14: ...13 Figure 3 Charge Controller Wiring Diagram with an FX HUB 4 and an RTS...
Страница 15: ...14 Figure 4 Charge Controller with PV array ground fault protection wiring digram...
Страница 37: ...36 Figure 5 Diversion Load and AUX Wiring Set Up Illustrated...