PB
Press the
<TIME>
soft key to advance to the
Time
screen which allows the user to adjust the minimum
time the
AUX MODE
is active after the battery voltage
falls below the Hysteresis voltage.
Hold Time
shows how long the
AUX MODE
stays active
after the battery voltage has fallen below the HYST
(Hysteresis) set point. The user can adjust the
Hold Time
from 0.1 to 25 seconds.
The
Delay Time
shows how long the battery voltage
must be above the
Relative Volts
before the
AUX MODE
is activated. It can be adjusted from 0 to 24 seconds,
but is rarely required
. Pressing the <
BACK
> soft key
returns to the
AUX MODE
Diversion:
Relay TIME
and
VOLT
screen.
Press the
<VOLT>
soft key.
Use this screen to establish the set points for starting
and ending the AUX MODE relative to the
Absorb
,
Float
,
and
EQ
voltages. The
< - >
and
< + >
soft keys set the
Diversion
set points. The
<HYST>
(Hysteresis) set point
establishes when the
AUX MODE
becomes inactive after
the battery voltage falls below the
Relative Volts
voltage
minus the HYST value. After establishing these values,
press the
<BACK>
soft key to return to the
Diversion:
Relay
TIME
and
VOLT
screen.
AUX MODE
Diversion: Relay
EXIT TIME VOLT
Hold
Delay
01.0
Time
00
seconds
BACK - + DLY+
AUX MODE
Diversion: Relay
EXIT TIME VOLT
Absorb--Float--EQ
Relative Volts
0.0 00.2
BACK - + HYST
g
g
Содержание FLEXMAX 80
Страница 9: ...THE OUTBACK POWER SYSTEMS FLEXmax 80 Maximum Power Point Tracking Charge Controller...
Страница 13: ...12 Figure 2 Single Charge Controller wiring diagram with 24 volt PV array...
Страница 14: ...13 Figure 3 Charge Controller Wiring Diagram with an FX HUB 4 and an RTS...
Страница 15: ...14 Figure 4 Charge Controller with PV array ground fault protection wiring digram...
Страница 37: ...36 Figure 5 Diversion Load and AUX Wiring Set Up Illustrated...