PB
• Are the batteries charged? Is the FLEXmax 80 in the
Absorbing
or
Float
stage? If either case is
true, the FLEXmax 80 will produce enough power to regulate the voltage at the
ABSORB
or
FLOAT
set point voltage, therefore, requiring less power in these modes.
• What is the short circuit current of the PV array? Use a multi-meter to determine if a short circuit
current is as expected. There might be a loose PV array connection.
• If the PV array voltage close to the battery voltage, the panels could be warm/hot causing the
Maximum Power Point to be at or lower than the battery voltage.
• Is it in
U-Pick
mode?
FLEXmax 80 is not equalizing
• Has the
EQ
cycle been initiated?
• In the EQ Menu, press START to begin process. When the EQ cycle has been initiated,
EQ-MPPT
will be displayed.
• The EQ cycle has been initiated, but the battery is not equalizing.
• The
EQ
cycle will begin when the target
EQ
set point voltage has been reached. A small
array or cloudy weather will delay the
EQ
cycle. Accordingly, running too many AC and/or
DC loads will delay the
EQ
cycle, too.
• An EQ set point that is too high relative to the battery voltage will delay the
EQ
cycle.
• If the PV array voltage is close to the battery voltage, the panels could be warm/hot causing the
Maximum Power Point to be at or lower than the battery voltage which can delay the
EQ
cycle.
FLEXmax 80 Battery Temperature Compensated Voltage
• Only the OutBack RTS (remote temperature sensor) can be used with the FLEXmax 80.
• The battery voltage can rise above the
ABSORBING
and
FLOAT
voltage set points if the battery
temperature is < 77°F or fall below the
ABSORBING
and
FLOAT
voltage if the battery temperature
is > 77°F.
• Why does the FLEXmax 80 show
BatTmpErr
on the
STATUS
screen?
• The RTS is faulty or damaged. Disconnect the RTS from the RTS jack to resume
normal operation.
Содержание FLEXMAX 80
Страница 9: ...THE OUTBACK POWER SYSTEMS FLEXmax 80 Maximum Power Point Tracking Charge Controller...
Страница 13: ...12 Figure 2 Single Charge Controller wiring diagram with 24 volt PV array...
Страница 14: ...13 Figure 3 Charge Controller Wiring Diagram with an FX HUB 4 and an RTS...
Страница 15: ...14 Figure 4 Charge Controller with PV array ground fault protection wiring digram...
Страница 37: ...36 Figure 5 Diversion Load and AUX Wiring Set Up Illustrated...