Absorb Time Limits
01.0 hours
EXIT NEXT - +
In the
Absorb Time Limits
screen, the user can set the
duration the FLEXmax 80 stays in the
Absorb
recharge
cycle.
•
Absorb Time
is adjustable from 0 to 24 hours (consult
your battery manufacturer’s recommendations).
• A
Bulk
cycle starts each morning (see chart next page).
The charge timer (ChgT) is preset to zero.
• The
ChgT
counts up to the Absorb Time Limit after the
Absorb voltage is reached.
• If the system cannot maintain the Absorb voltage
set point during the
Absorb
cycle, the timer will stop
counting up.
• If the battery voltage is greater than or equal to 12.4V,
24.8V, 37.2V, 49.6V 62.0V and less than the absorb
voltage, the
ChgT
timer does not change.
• If the battery voltage is less than 12.4 V, 24.8V, 37.2V,
49.6V or 62.0V, the
ChgT
timer counts down to zero
in minutes—for every minute elapsed, one minute is
subtracted from the timer.
• If the battery voltage is less than 12.0V, 24.0V, 36.0V,
48.0V or 60.0V, the
ChgT
timer counts down to zero at
twice as fast—for every minute elapsed, two minutes is
subtracted from the timer.
• If the battery voltage is less than 11.6V, 23.2V, 34.8V,
46.6V, or 58.0V, the
ChgT
timer counts to zero four
times as fast—for every minute elapsed, four minutes
is subtracted from the timer.
• When the
Absorb Time Limit
is reached, the FLEXmax 80
goes into
Float
stage and may briefly display
Charged
then
Float.
When the battery voltage drops below the
float voltage set point, the FLEXmax 80 recharges to
maintain this set point, employing the
F(Float)-MPPT
function.
To adjust the
Absorb Time
limit, press either the
< + >
or
< ->
soft key. When finished, press the
<NEXT>
soft key to view the next screen.
. Charging-Related Screens
Содержание FLEXMAX 80
Страница 9: ...THE OUTBACK POWER SYSTEMS FLEXmax 80 Maximum Power Point Tracking Charge Controller...
Страница 13: ...12 Figure 2 Single Charge Controller wiring diagram with 24 volt PV array...
Страница 14: ...13 Figure 3 Charge Controller Wiring Diagram with an FX HUB 4 and an RTS...
Страница 15: ...14 Figure 4 Charge Controller with PV array ground fault protection wiring digram...
Страница 37: ...36 Figure 5 Diversion Load and AUX Wiring Set Up Illustrated...