PB
BULK cycle provides the maximum power to the battery –the voltage increases while recharging.
A Bulk cycle is automatically initiated when the battery voltage is below the
Absorb
and
Float
* recharge
voltage set points. The
Bulk
cycle will continue until the
Absorb
voltage set point is achieved.
MPPT Bulk
is displayed on the screen.
ABSORBING cycle limits the amount of power going to the battery—the voltage is held constant.
The
Absorb
cycle will continue for the duration of the
Bulk
cycle or until the 2 hour (default)
Absorb
time limit is reached. For example, if a
Bulk
cycle takes 1 hour to reach the
Absorb
voltage set point,
then the
Absorb
cycle will continue for 1 hour as well. However, if a Bulk cycle takes 3 hours to reach
the
Absorb
voltage set point, then the
Absorb
cycle will continue for 2 hours only. A
Bulk
cycle will be
re-initiated if the battery voltage is not sustained at the
Absorb
voltage set point.
Absorbing
is displayed
on the screen at this time.
FLOAT cycle reduces the recharging voltage to prevent overcharging of the batteries.
A
Float
cycle follows after the
Absorb
cycle is completed;
Float
is displayed on the screen. The
FLEXmax 80
will not
re-initiate another
Bulk
cycle if the
Float
voltage set point is not sustained*.
FMPPT is displayed. However, it will continue to recharge the battery until the
Float
voltage set point is
reached.
* A
Bulk
cycle can be auto-initiated if the battery voltage falls below the
Float
voltage set point and the
Re-Bulk
voltage option is set.
Содержание FLEXMAX 80
Страница 9: ...THE OUTBACK POWER SYSTEMS FLEXmax 80 Maximum Power Point Tracking Charge Controller...
Страница 13: ...12 Figure 2 Single Charge Controller wiring diagram with 24 volt PV array...
Страница 14: ...13 Figure 3 Charge Controller Wiring Diagram with an FX HUB 4 and an RTS...
Страница 15: ...14 Figure 4 Charge Controller with PV array ground fault protection wiring digram...
Страница 37: ...36 Figure 5 Diversion Load and AUX Wiring Set Up Illustrated...