Page
179
of
248
:HG 3 #15 10.20 10.15 :PC 1 #15 50 49 :TA 0 #15 -22.1 -22.0 :VB 0 12.2
In the example above
:HG 3 #15 10.20 10.15
means that the sensor labeled HG read the value 10.20 three
minutes prior to the start of the transmission. It read 10.15 18 minutes before the start of the
transmission, or 15 minutes before it read 10.20. Here is the complete decode:
:HG
Measurement labled HG
3
Reading is 3 minutes old
#15
15 minute measurement interval
10.20
HG sensor reading (most recent)
10.15
HG sensor reading
:PC
Measurement labled PC
1
Reading is 1 minute old
#15
15 minute measurement interval
50
PC sensor reading (most recent)
49
PC sensor reading
:TA
Measurement labled TA
0
Reading is less than one minute old
#15
15 minute measurement interval
-22.1
TA sensor reading (most recent)
-22.0
TA sensor reading
:VB
Battery voltage label
0
Reading is less than one minute old
12.2
Battery voltage reading
SHEFFIX is a modified version of SHEF where the data is positioned in fixed spacing so that it will line up
better when displayed. Each measurement reading is given seven bytes. If a reading uses fewer bytes, it is
padded with spaces. SHEIFIX transmissions are larger than SHEF transmissions.
SHEFFIX Example
:STAGE 0 #2 20.50 20.50 20.50 20.50 :PRECIP 3 #5 12.00 12.01 :TEMP 3 #5 23.5 23.2
:BV 1 #3 14
SHEF Example with Min/Max data included
When transmitting Min/Max data, the formatter includes a timestamp for each value because the
Min/Max data is logged at the time of the occurrence rather than the measurement interval. Note how in
the message below the MX and MN only have one value and the timestamp is different for each.
:ITEMP 12 #15 25.9018 26.0289 26.0988 26.2451
:MX 64 #60 26.686
:
MX 101 #60 27.426
:
MN 14 #60
25.891
:
MN 131 #60 25.334
:AVG 12 #60 26.169 26.368