Modbus
registers
Last
Measured
measurement
msw
lsw
M1
1
2
M2
3
4
M3
5
6
M4
7
8
M5
9
10
M6
11
12
M7
13
14
M8
15
16
M9
17
18
M10
19
20
M11
21
22
M12
23
24
M13
25
26
M14
27
28
M15
29
30
M16
31
32
..
M32
63
64
Battery Voltage
901
902
Internal Temp
903
904
M1, M2, .. M32 refer to measurements.
E.g., to read the last measured sensor value for measurement M10, read registers 19 and 20 and combine
the result into a single 32 bit IEEE floating point value.
19.4.2
Calibrating Measurements by Writing to Modbus Registers
It is possible to write to the station’s
Modbus Holding Registers in order to calibrate measurements.
Modbus Holding Registers 1 and 2 will map to measurement M1 and be interpreted as a float (register 1 is
MSW, 2 is LSW). Registers 3 and 4 map to M2 in the same way. Please see the table above for a complete
register map.
Writing to the Modbus Holding Registers will be treated like a measurement calibration.
If the Measurement Type is Manual Entry, writing to the corresponding registers will simply
update the measured value to the received value.
The values written to the Registers will be logged and transmitted just like other sensor readings.
To use this feature, setup the system as a Modbus Server. No further setup is needed.