To send a command to an SDI-12 device, enter the
Address
and
Command
fields, and then press the
Send
button. Be sure to select the proper port. The results of the command are shown in the SDI-12 history
window.
To have the station look for any and all sensors on the SDI-12 bus, press the
Find Devices
button.
Information regarding what sensors are found is displayed in the SDI-12 history window.
Press the
Clear
button to clear the SDI-12 history window.
10.3.4
Measure Type: Analog
Analog measurements involve reading a voltage or current provided by a sensor. Analog sensors come
with instructions that provide information on how to translate the output voltage into desired units.
Translating the analog sensor output into environmental units can be done via slope and offset for simple
sensors, and via equations for non-linear sensors.
Analog measurements are available on select models.
Analog Type
This setting directs the input channel to which the sensor should be connected and the type of analog
measurement to make. These options are available
0-5V A
0-5V B
Diff C
Diff D
4-20 mA