10.6
Alarm Computation Details
This section contains details on how the system decides whether to go into alarms. The section is broken
down by the user chosen
Alarm Type
setting:
10.6.1
Hi Alarm
When the Alarm Type is set to Hi, if the sensor reading is greater than or equal to Alarm Threshold, the
station goes into alarm.
That station will go out of alarm when the sensor reading goes below Alarm Threshold minus Alarm
Deadband.
Hi alarm scenario:
System measures stage every 15 min
Hi Alarm threshold is at 2ft
Tx Alarm Interval is 5min
Once stage exceeds 2ft, the system sends out an alarm transmission
As long as stage is above 2ft, the system will send out alarm transmissions every 5min
Note how even though the measurement interval is 15min, the transmissions are fired off every
5min
10.6.2
Low Alarm
When the Alarm Type is set to Low, if the sensor reading is less than or equal to Alarm Threshold, the
station goes into alarm.
That station will go out of alarm when the sensor reading goes above Alarm Threshold plus Alarm
Deadband.
10.6.3
ROC Alarm
ROC stands for Rate Of Change. ROC alarms compare the current measurement reading with a past
reading. If
Alarm ROC Interval
is
Since Last Meas
, the past reading is the last scheduled reading made
according to
Measurement Time
and
Measurement Interval.
If
Alarm ROC Interval
is
Since Last Tx
, the past reading is the one that was included in the last alarm
transmission. If there is no past transmission, the first reading made after boot up is used.
If the absolute difference between the two readings (absolute of current reading minus past reading) is
greater or equal to the
Alarm Threshold
, the station goes into alarm.
The same station goes out of alarm if the absolute difference between the two readings (absolute of
current reading minus past reading) is less than the
Alarm Threshold
minus
Alarm Deadband.
Exception:
ROC alarms setup for
Since Last Tx
do not generate out of alarm events or transmissions.