Grounding the CPU Rack
This section describes how to ground the ground terminals on the CPU Rack.
The functional ground terminals that are provided on some Units and the DIN Track are grounded.
NX1P2
CPU Unit
DIN Track
Additional
NX Unit
Power
Supply Unit
Shield
Connec-
tion Unit
Functional ground
terminal
Ground
Electrically connected to the DIN Track
through the DIN Track contact plate.
Functional ground
terminal
Functional ground
terminal
End Cover
○
○
○
• Using a dedicated ground wire, ground the ground terminals and DIN Track with a ground resist-
ance of 100 Ω or less.
• The ground wire should not be more than 20 m long.
• Use a ground wire that is 2.0 mm
2
or larger. Refer to
5-4-8 Wiring to the CPU Unit Terminal Block
page 5-51 for information on ground wires that are applicable to the functional ground terminal on
the CPU Unit. For information on ground wires that are applicable to the functional ground terminals
on the Additional NX Unit Power Supply Unit or Shield Connection Unit, refer to the
NX-series
System Units User’s Manual
(Cat. No. W523).
If the DIN Track is made of steel and the surface is not treated to produce an insulating material, you
can omit grounding the functional ground terminal on any Unit that has one, as shown in the following
figures.
NX1P2
CPU Unit
DIN Track
Additional
NX Unit
Power
Supply Unit
Shield
Connec-
tion Unit
Functional ground
terminal
Ground
Electrically connected to the DIN Track
through the DIN Track contact plate.
Functional ground
terminal
Functional ground
terminal
End Cover
○
○
○
If the surface of the DIN Track is treated to produce an insulating material (e.g., anodized aluminum),
the DIN Track contact plate will not be electrically connected to the DIN Track even if they are in physi-
cal contact.
Grounding the DIN Track
Attach a crimped terminal to the ground wire and then connect it to mounting hole on the DIN Track
with a screw to ground the DIN Track.
5 Installation and Wiring
5-48
NX-series NX1P2 CPU Unit Hardware User’s Manual (W578)
Содержание NX1P2 series
Страница 8: ...Manual Structure 6 NX series NX1P2 CPU Unit Hardware User s Manual W578...
Страница 52: ...Revision History 50 NX series NX1P2 CPU Unit Hardware User s Manual W578...
Страница 82: ...2 System Configuration 2 10 NX series NX1P2 CPU Unit Hardware User s Manual W578...
Страница 170: ...a b Flat blade screwdriver 1 2 5 Installation and Wiring 5 26 NX series NX1P2 CPU Unit Hardware User s Manual W578...
Страница 174: ...4 Close the Memory Card cover 5 Installation and Wiring 5 30 NX series NX1P2 CPU Unit Hardware User s Manual W578...
Страница 176: ...4 Close the Memory Card cover 5 Installation and Wiring 5 32 NX series NX1P2 CPU Unit Hardware User s Manual W578...
Страница 224: ...0 4 mm Side view Front view 2 5 mm 5 Installation and Wiring 5 80 NX series NX1P2 CPU Unit Hardware User s Manual W578...
Страница 258: ...Appendices A 10 NX series NX1P2 CPU Unit Hardware User s Manual W578...
Страница 259: ...I Index I 1 NX series NX1P2 CPU Unit Hardware User s Manual W578 I...
Страница 262: ...Index I 4 NX series NX1P2 CPU Unit Hardware User s Manual W578...
Страница 263: ......