Routing Wiring Ducts
Install the wiring ducts at least 20 mm away from the tops of the Rack and any other objects (e.g.,
ceiling, wiring ducts, structural supports, devices, etc.) to provide enough space for air circulation
and replacement of Units.
Breakers,
fuses
Power
equipment
such as
transformers
and magnetic
relays
Terminal blocks for
power equipment
Terminal blocks
for PLC
Fuses, relays, timers, etc.
(Do not install devices that
generate heat or power
equipment.)
NX-series
Controller
Input duct
Output duct
200 mm min.
Power duct
EtherCAT
Slave Terminal, etc.
5 Installation and Wiring
5-15
NX-series NX1P2 CPU Unit Hardware User’s Manual (W578)
5-3
Mounting and Removing Units
5
5-3-1
Installation in a Control Panel
Содержание NX1P2 series
Страница 8: ...Manual Structure 6 NX series NX1P2 CPU Unit Hardware User s Manual W578...
Страница 52: ...Revision History 50 NX series NX1P2 CPU Unit Hardware User s Manual W578...
Страница 82: ...2 System Configuration 2 10 NX series NX1P2 CPU Unit Hardware User s Manual W578...
Страница 170: ...a b Flat blade screwdriver 1 2 5 Installation and Wiring 5 26 NX series NX1P2 CPU Unit Hardware User s Manual W578...
Страница 174: ...4 Close the Memory Card cover 5 Installation and Wiring 5 30 NX series NX1P2 CPU Unit Hardware User s Manual W578...
Страница 176: ...4 Close the Memory Card cover 5 Installation and Wiring 5 32 NX series NX1P2 CPU Unit Hardware User s Manual W578...
Страница 224: ...0 4 mm Side view Front view 2 5 mm 5 Installation and Wiring 5 80 NX series NX1P2 CPU Unit Hardware User s Manual W578...
Страница 258: ...Appendices A 10 NX series NX1P2 CPU Unit Hardware User s Manual W578...
Страница 259: ...I Index I 1 NX series NX1P2 CPU Unit Hardware User s Manual W578 I...
Страница 262: ...Index I 4 NX series NX1P2 CPU Unit Hardware User s Manual W578...
Страница 263: ......