Standard System Configuration
3-30
Part 1056418-07
E
2019 Nordson Corporation
Prodigy HDLV Pump Calibration
See Figure 3-28. This function is only available to Nordson CSRs or field
engineers. Touching the
Pump Calibration
button on the System
Configuration screen opens the Calibration screen.
Each spray gun has its own HDLV pump, located on a pump panel. Inside
the panel are the pump control board and manifold. On each pump
manifold is a label with Pump Flow and Pattern Flow A, B, and C calibration
constants which must be entered into the Pump Calibration screen.
Calibration Procedure:
1. Select spray gun number 1.
2. Enter the calibration numbers on the pump manifold label for the gun 1
pump.
3. Touch
Send
.
4. Repeat for each spray gun/pump combination.
NOTE:
If you replace a pump control manifold or pump control board you
must use this screen to enter the new manifold calibration numbers.
Figure 3-28 HDLV Pump Calibration
Содержание Encore iControl 2
Страница 8: ...Table of Contents vi Part 1056418 07 E 2019 Nordson Corporation...
Страница 10: ...Change Record viii Part 1056418 07 E 2019 Nordson Corporation...
Страница 116: ...Positioner Preset Settings 6 8 Part 1056418 07 E 2019 Nordson Corporation...
Страница 142: ...Operation 8 20 Part 1056418 07 E 2019 Nordson Corporation...
Страница 168: ...Configuration and Preset Records 10 12 Part 1056418 07 E 2019 Nordson Corporation...