Conveyor Speed Percent Adjust
Conveyor Speed Percent Adjust works as follows, using the example in
The
nominal
conveyor speed is 16 ft/min. As long as the conveyor speed
stays within the
dead band
(
±
2%, or
±
0.2 ft/min., or 15.68
−
16.32 ft/min.)
nothing happens. If the conveyor speed increases past 16.32 ft/min. then
flows are increased linearly until at 18 ft/min. both flow settings have been
increased by 10%.
If the conveyor speed decreases below 9.8 ft/min. and keeps decreasing,
then flows are decreased linearly until at 8 ft/min. both flow settings have
been decreased by 20%. If the conveyor speed goes above 18 ft/min. the
adjustment stays at 10%; if it goes below 8 ft/min. the adjustment stays at
20%.
To turn the Conveyor Speed Percent Adjust function off, touch the
Enable/Disable selection box.
OFF
ON
Flow-rate Air
or Powder Flow
% Adjust Limit
% Atomizing Air
or Pattern Air
Enable/
Disable
Fast
Nominal
Slow
Dead Band
Global
% Adjust
Conveyor
% Adjust
Speed
% Flow
% Speed
Atomizing Air
or Pattern Air
% Adjust Limit
% Flow-rate Air
or Powder Flow
Figure 8-8
Percent Adjust Screen
Содержание Encore iControl 2
Страница 8: ...Table of Contents vi Part 1056418 07 E 2019 Nordson Corporation...
Страница 10: ...Change Record viii Part 1056418 07 E 2019 Nordson Corporation...
Страница 116: ...Positioner Preset Settings 6 8 Part 1056418 07 E 2019 Nordson Corporation...
Страница 142: ...Operation 8 20 Part 1056418 07 E 2019 Nordson Corporation...
Страница 168: ...Configuration and Preset Records 10 12 Part 1056418 07 E 2019 Nordson Corporation...