2.4 Grounding and Power Connections
KP3000GS
11
About power input terminal
Table 2-4 Power Input Terminal
KP3000GS
Screw M6
About power input cable
The power input cable supplied with this product varies in diameter as shown in Table 2-5. A
crimp-type terminal is attached to each cable on the end which is to be connected to the input
terminal of this product.
On the supplied power input cable, the end which is to be connected to the distribution board
has no terminal attached. Use a crimp-type terminal appropriate for the terminal screw
diameter of the distribution board to connect the cable firmly.
The supplied power input cable is dedicated only to this product. Do not use it with any other
product.
When you use a power input cable other than the one supplied with the product, select a cable
which has an appropriate diameter in consideration of the safety standards and consumption
current. Use a protective grounding conductor of which diameter is the same or greater than
the power input cable.
Table 2-5 Maximum Input Power/Current and Power Input Cable
Rated
output
Maximum
Input
Power
Maximum
Input Current
Supplied power input cable
Power
Input
90 V
Power
Input
170 V
For both 100 V and 200 V series
(Power Input 90 V or More)
Only for 200 V Series
(Power Input 170 V or More)
3 kVA
4.50 kVA
50 A
26 A
14 mm
2
approx.
5.5 mm
2
approx.
Power source connection procedure
Check the current capacity of the single-phase distribution board before wiring. The wiring must be
performed by a professional engineer.
Before connecting this product to the power source, be sure to cut the power to the distribution
board. Otherwise, an electric shock might occur.
WARNING
Содержание KP3000GS
Страница 1: ...PROGRAMMABLE AC DC POWER SOURCE KP3000GS INSTRUCTION MANUAL...
Страница 2: ......
Страница 3: ...DA00033845 005 PROGRAMMABLE AC DC POWER SOURCE KP3000GS INSTRUCTION MANUAL...
Страница 4: ......
Страница 5: ......
Страница 19: ......
Страница 20: ...KP3000GS 1 1 Outline 1 1 Overview 2 1 2 Features 2...
Страница 23: ......
Страница 197: ......
Страница 198: ...KP3000GS 179 5 Description of Screen and Menu 5 1 Screen Configuration 180 5 2 Menu Composition 184...
Страница 207: ......
Страница 208: ...KP3000GS 189 6 Remote Control 6 1 Communication Interface 190 6 2 Remote Local State Switching 199...
Страница 219: ......
Страница 224: ...KP3000GS 205 8 Troubleshooting 8 1 Error Messages and Error Handling 206 8 2 When a Failure is Suspected 213...
Страница 243: ......
Страница 275: ......
Страница 277: ......
Страница 278: ......
Страница 279: ...http www nfcorp co jp NF Corporation 6 3 20 Tsunashima Higashi Kohoku ku Yokohama 223 8508 JAPAN...