6 Mounting
Maschinenfabrik Reinhausen GmbH 2020
68
4453918/14 EN
ETOS
®
TD
4. Connect the shield of the connection cable provided (electrical connection
between control cabinet and gear motor) using shielded clamps on the
grounding bar in the control cabinet.
Figure 54: Connection of the shielded clamps on the grounding bar of the control cabinet
1 Grounding bar
Tighten cable screw connections on control cabinet to the following tighten-
ing torques: M20: 8 Nm, M32: 20 Nm.
5. Optional: Connect digital inputs and outputs, analog sensors, voltage
measurement and current measurement of the transformer in accordance
with the connection diagram. For shielded cables, place the cable shield
on the grounding bar in the control cabinet.
6. Connect the power supply of the control cabinet in accordance with the
connection diagram provided.
7. Engage the motor protective switch Q1 in the control cabinet.