9 Visualization
Maschinenfabrik Reinhausen GmbH 2020
199
4453918/14 EN
ETOS
®
TD
Delay time
You can use this parameter to set the delay time in order to delay the issuing
of the event message.
Reaction
You can use this parameter to set the behavior of the device if the measured
value is higher than the upper limit (> or >>) or lower than the lower limit (<
or <<). You can select the following options:
Setting
Behavior
Off
No reaction.
Auto blocking
Automatic regulation is blocked.
You can continue to perform tap-change operations in
manual mode.
Auto/manual blocking
Automatic regulation is blocked.
You
cannot
perform tap-change operations in manual
mode.
Table 67: Behavior when an event message is issued
9.22.3 Power monitoring
For monitoring the transformer's current power, you can set the following
limit values:
Measured value
Lower
limit 2
Lower
limit 1
Upper
limit 1
Upper
limit 2
Apparent power
S<<
S<
S>
S>>
Active power
P<<
P<
P>
P>>
Reactive power
Q<<
Q<
Q>
Q>>
Power factor (amount)
|cos φ|<<
|cos φ|<
-
-
Table 68: Limit values for power monitoring
You can set the following parameters for each limit value:
▪ Limit value: Absolute limit value
▪ Hysteresis limit value
▪ Delay time limit value
▪ Behavior limit value (only for devices with voltage regulation)
Содержание ETOS TD
Страница 1: ...Motor drive unit ETOS TD Operating Instructions 4453918 14 EN ...
Страница 329: ...15 Technical data Maschinenfabrik Reinhausen GmbH 2020 329 4453918 14 EN ETOS TD 15 2 2 Drawings 15 2 2 1 ETOS TD S ...
Страница 330: ......
Страница 331: ...15 Technical data Maschinenfabrik Reinhausen GmbH 2020 331 4453918 14 EN ETOS TD 15 2 2 2 ETOS TD L ...
Страница 332: ......
Страница 333: ...15 Technical data Maschinenfabrik Reinhausen GmbH 2020 333 4453918 14 EN ETOS TD 15 2 2 3 ETOS TD XL ...
Страница 334: ......
Страница 355: ......