9 Visualization
Maschinenfabrik Reinhausen GmbH 2020
127
4453918/14 EN
ETOS
®
TD
The following diagrams show an example of a graph of the fan speeds
based on the load factor according to the set parameters.
10
20
30
40
50
100
%
0
20
40
60
120
140
%
n
60
70
80
80
100
0
n
n
min
max
L
L
S1
S2
I
L
/
n
I
Load factor
Figure 91: Fan speed based on load factor
n Fan speed
θ
Top-oil
Temperature of top-oil
n
min
Minimum fan speed
n
max
Maximum fan speed
L
S1
Lower load factor threshold
L
S2
Upper load factor threshold
Settings
Parameters
Cooling sy...rol
Name
Value
Min. fan run time after error
300 s
Minimum fan speed
10 %
Maximum fan speed
100 %
Lower threshold for top-oil temp.
20°C
Upper threshold for top-oil temp.
60°C
Lower load factor threshold
0 %
Upper load factor threshold
100 %
Home
Events
Information
Recorder
Settings
EN
CHANGE
REBOOT
admin
05.02.2020 10:09
Figure 92: Frequency-based cooling system control
1. Go to
Settings > Parameters > Cooling system > Cooling system con-
trol
.
2. Select the desired parameter.
3. Set the parameter.
4. Press the
Accept
button to save the modified parameter.
Содержание ETOS TD
Страница 1: ...Motor drive unit ETOS TD Operating Instructions 4453918 14 EN ...
Страница 329: ...15 Technical data Maschinenfabrik Reinhausen GmbH 2020 329 4453918 14 EN ETOS TD 15 2 2 Drawings 15 2 2 1 ETOS TD S ...
Страница 330: ......
Страница 331: ...15 Technical data Maschinenfabrik Reinhausen GmbH 2020 331 4453918 14 EN ETOS TD 15 2 2 2 ETOS TD L ...
Страница 332: ......
Страница 333: ...15 Technical data Maschinenfabrik Reinhausen GmbH 2020 333 4453918 14 EN ETOS TD 15 2 2 3 ETOS TD XL ...
Страница 334: ......
Страница 355: ......