12 Event messages
Maschinenfabrik Reinhausen GmbH 2020
322
4453918/14 EN
ETOS
®
TD
No.
Name
Description
Remedy
1101 Transformer oil level
<< limit value
Oil level of transformer is less
than << limit value.
Check the transformer oil level and the device
wiring. If using an analog sensor, check the sen-
sor, analog signal configuration, and the set limit
value.
1106 OLTC oil temperature
> limit value
Oil temperature of on-load tap-
changer is greater than > limit
value.
Check the current operating conditions of the
on-load tap-changer, temperature sensor, ana-
log signal configuration, and the set limit value.
1107 OLTC oil temperature
>> limit value
Oil temperature of on-load tap-
changer is greater than >> limit
value.
Check the current operating conditions of the
on-load tap-changer, temperature sensor, ana-
log signal configuration, and the set limit value.
1108 OLTC oil temperature
< limit value
Oil temperature of on-load tap-
changer is less than < limit value.
Check the current operating conditions of the
on-load tap-changer, temperature sensor, ana-
log signal configuration, and the set limit value.
1109 OLTC oil temperature
<< limit value
Oil temperature of on-load tap-
changer is less than << limit
value.
Check the current operating conditions of the
on-load tap-changer, temperature sensor, ana-
log signal configuration, and the set limit value.
1112 Upper oil temperature
> limit value
Upper oil temperature is greater
than > limit value.
Check the current operating conditions of the
transformer, temperature sensor, analog signal
configuration, and the set limit value.
1113 Upper oil temperature
>> limit value
Upper oil temperature is greater
than >> limit value.
Check the current operating conditions of the
transformer, temperature sensor, analog signal
configuration, and the set limit value.
1114 Upper oil temperature
< limit value
Upper oil temperature is less than
< limit value.
Check the current operating conditions of the
transformer, temperature sensor, analog signal
configuration, and the set limit value.
1115 Upper oil temperature
<< limit value
Upper oil temperature is less than
<< limit value.
Check the current operating conditions of the
transformer, temperature sensor, analog signal
configuration, and the set limit value.
1121 OLTC oil temperature
invalid
The analog signal for recording
the on-load tap-changer's oil tem-
perature is invalid.
Check the sensor, device wiring, and analog
signal configuration.
1123 Upper oil temperature
invalid
The analog signal for recording
the upper oil temperature is in-
valid.
Check the sensor, device wiring, and analog
signal configuration.
1145 Plan OLTC mainte-
nance
OLTC maintenance is required
soon.
Undertake the OLTC maintenance soon.
1146 OLTC maintenance is
required
The OLTC maintenance is re-
quired.
Undertake the OLTC maintenance.
1147 Plan OLTC replace-
ment
The OLTC replacement is re-
quired soon.
Undertake the OLTC replacement soon.
1148 OLTC replacement is
required
The OLTC replacement is re-
quired.
Undertake the OLTC replacement.
1149 Plan DSI replacement
The DSI replacement is required
soon.
Undertake the DSI replacement soon.
1150 DSI replacement is re-
quired
The DSI replacement is required.
Undertake the DSI replacement.
Содержание ETOS TD
Страница 1: ...Motor drive unit ETOS TD Operating Instructions 4453918 14 EN ...
Страница 329: ...15 Technical data Maschinenfabrik Reinhausen GmbH 2020 329 4453918 14 EN ETOS TD 15 2 2 Drawings 15 2 2 1 ETOS TD S ...
Страница 330: ......
Страница 331: ...15 Technical data Maschinenfabrik Reinhausen GmbH 2020 331 4453918 14 EN ETOS TD 15 2 2 2 ETOS TD L ...
Страница 332: ......
Страница 333: ...15 Technical data Maschinenfabrik Reinhausen GmbH 2020 333 4453918 14 EN ETOS TD 15 2 2 3 ETOS TD XL ...
Страница 334: ......
Страница 355: ......