9 Visualization
Maschinenfabrik Reinhausen GmbH 2020
244
4453918/14 EN
ETOS
®
TD
9.27.2.4 Duval analysis
The display of the Duval analysis shows the following information:
▪ Duval triangle, with the allocation of the last 10 measured values in the ar-
eas of the various error types.
– Latest measured value: Darkest area with a display of the measure-
ment error.
– Earliest measured value: Lightest area
▪ Display of the error types. The error type of the latest measured value is
highlighted in white.
▪ Gas concentrations of the latest measured value
If you call up the visualization using a PC, the gas concentrations and the
time of the measurement are displayed for each measured value via tooltip.
Figure 177: Display of the Duval analysis
► Go to
Information > Active part > DGA > Duval
.
9.27.2.5 Rogers analysis
The display of the Rogers analysis shows the following information:
▪ 3D diagram, with the allocation of the last 10 measured values in the ar-
eas of the various error types.
– Latest measured value: Darkest area with a display of the measure-
ment error.
– Earliest measured value: Lightest area
▪ Display of the error types. The error type of the latest measured value is
highlighted in white.
▪ Proportion of the gas concentrations of the latest measured value
Содержание ETOS TD
Страница 1: ...Motor drive unit ETOS TD Operating Instructions 4453918 14 EN ...
Страница 329: ...15 Technical data Maschinenfabrik Reinhausen GmbH 2020 329 4453918 14 EN ETOS TD 15 2 2 Drawings 15 2 2 1 ETOS TD S ...
Страница 330: ......
Страница 331: ...15 Technical data Maschinenfabrik Reinhausen GmbH 2020 331 4453918 14 EN ETOS TD 15 2 2 2 ETOS TD L ...
Страница 332: ......
Страница 333: ...15 Technical data Maschinenfabrik Reinhausen GmbH 2020 333 4453918 14 EN ETOS TD 15 2 2 3 ETOS TD XL ...
Страница 334: ......
Страница 355: ......