9 Visualization
Maschinenfabrik Reinhausen GmbH 2020
201
4453918/14 EN
ETOS
®
TD
Setting
Behavior
Auto blocking position-
The automatic control does not perform a tap-change
operation in the direction of a lower tap position (posi-
tion-).
You can continue to perform tap-change operations in
manual mode.
Auto blocking p
The automatic control does not perform a tap-change
operation in the direction of a higher tap position (posi-
tion+).
You can continue to perform tap-change operations in
manual mode.
Auto/manual blocking
Automatic regulation is blocked.
You
cannot
perform tap-change operations in manual
mode.
Auto/manual blocking po-
sition-
The automatic control does not perform a tap-change
operation in the direction of a lower tap position (posi-
tion-).
You
cannot
perform a tap-change operation in the di-
rection of a lower tap position (position-) in manual
mode.
Auto/manual blocking po-
The automatic control does not perform a tap-change
operation in the direction of a higher tap position (posi-
tion+).
You
cannot
perform a tap-change operation in the di-
rection of a higher tap position (p) in manual
mode.
Table 69: Behavior when an event message is issued
9.22.4 Power flow monitoring
A reversal of power flow occurs if the active power is negative. You can set
the following parameters for this:
▪ Hysteresis
▪ Delay time
▪ Behavior
Содержание ETOS TD
Страница 1: ...Motor drive unit ETOS TD Operating Instructions 4453918 14 EN ...
Страница 329: ...15 Technical data Maschinenfabrik Reinhausen GmbH 2020 329 4453918 14 EN ETOS TD 15 2 2 Drawings 15 2 2 1 ETOS TD S ...
Страница 330: ......
Страница 331: ...15 Technical data Maschinenfabrik Reinhausen GmbH 2020 331 4453918 14 EN ETOS TD 15 2 2 2 ETOS TD L ...
Страница 332: ......
Страница 333: ...15 Technical data Maschinenfabrik Reinhausen GmbH 2020 333 4453918 14 EN ETOS TD 15 2 2 3 ETOS TD XL ...
Страница 334: ......
Страница 355: ......