9 Visualization
Maschinenfabrik Reinhausen GmbH 2020
230
4453918/14 EN
ETOS
®
TD
The device also shows the differences in contact wear for different contacts.
Figure 165: Contact wear
► Go to
Information > On-load tap-changer > Contact wear
.
9.25.6 Configuring OLTC PreCheck
The OLTC PreCheck function is used to prevent damage on the on-load tap-
changer by on-load tap-changer operations under unauthorized operating
conditions. OLTC PreCheck monitors compliance with the following limit val-
ues for this purpose:
▪ Overcurrent I>>
▪ Oil level OLTC >> and oil level OLTC << (optional)
▪ Oil temperature >> (optional)
If a measured value is greater than the limit value, the OLTC PreCheck pre-
vents an on-load tap-changer operation from taking place. OLTC PreCheck
blocks both manual tap position commands (S3 control switch, digital inputs,
SCADA) and automatic voltage regulation. The status of OLTC-PreCheck is
displayed in the "Information > Drive [
Section 9.12, Page 135]" display.
You can set the following parameters for the OLTC PreCheck:
▪ Activate OLTC PreCheck
▪ Limit values
– Oil level (optional)
– Oil temperature (optional)
– Overcurrent I>>
Содержание ETOS TD
Страница 1: ...Motor drive unit ETOS TD Operating Instructions 4453918 14 EN ...
Страница 329: ...15 Technical data Maschinenfabrik Reinhausen GmbH 2020 329 4453918 14 EN ETOS TD 15 2 2 Drawings 15 2 2 1 ETOS TD S ...
Страница 330: ......
Страница 331: ...15 Technical data Maschinenfabrik Reinhausen GmbH 2020 331 4453918 14 EN ETOS TD 15 2 2 2 ETOS TD L ...
Страница 332: ......
Страница 333: ...15 Technical data Maschinenfabrik Reinhausen GmbH 2020 333 4453918 14 EN ETOS TD 15 2 2 3 ETOS TD XL ...
Страница 334: ......
Страница 355: ......