9 Visualization
Maschinenfabrik Reinhausen GmbH 2020
296
4453918/14 EN
ETOS
®
TD
Figure 220: Example of RS
1 Trigger
2 Set
3 Reset
4 Output
9.38.1.3.8 Switch-on delay
Description
TON, switch-on delay
Inputs
Input (BOOL)
Outputs
Output (BOOL)
Parameter
Time ms (UINT32), 1...1,000,000, default = 1,000
Function
If Input has a rising edge, the internal timer is set to
zero and starts to run.
When the internal timer has reached or exceeded the
parameter value, Output becomes TRUE and the
counter stops running.
If Input becomes FALSE, Output also instantly be-
comes FALSE.
If the value of Time_ms is less than the cycle time, the
cycle time applies instead.
Initial state
All inputs and outputs are FALSE.
Table 103: Switch-on delay function module
9.38.1.3.9 Switch-off delay
Description
TOFF, switch-off delay
Inputs
Trigger (BOOL)
Reset (BOOL)
Outputs
Output (BOOL)
Parameter
Time ms (UINT32), 1...1,000,000, default = 1,000