9 Visualization
Maschinenfabrik Reinhausen GmbH 2020
139
4453918/14 EN
ETOS
®
TD
9.14.2 Setting control variable (optional)
If the device is equipped with the optional reactive power regulation function,
you can set which control variable the device is to regulate.
Settings
Parameters
Control
Name
Value
Control variable
Voltage
Response to SCADA disconnection
No reaction
SCADA disconnection delay time
5 s
Home
Events
Information
Recorder
Settings
EN
CHANGE
REBOOT
admin
23.09.2020 09:23
Figure 103: Regulation
1. Go to
Settings > Parameters > On-load tap-changer regulator > Regu-
lation
.
2. Select the desired parameter.
3. Set the desired parameter.
4. Press the
Accept
button to save the modified parameter.
Control variable
You can use this parameter to set which control variable the device is to reg-
ulate. You can select the following options:
▪ Voltage
▪ Reactive power
Depending on your selection, the device uses the associated parameter set
for each option (desired value, bandwidth, etc.).
Standard regulation mode
You can set use this parameter to set the operating mode of the on-load tap-
changer regulation.
Содержание ETOS TD
Страница 1: ...Motor drive unit ETOS TD Operating Instructions 4453918 14 EN ...
Страница 329: ...15 Technical data Maschinenfabrik Reinhausen GmbH 2020 329 4453918 14 EN ETOS TD 15 2 2 Drawings 15 2 2 1 ETOS TD S ...
Страница 330: ......
Страница 331: ...15 Technical data Maschinenfabrik Reinhausen GmbH 2020 331 4453918 14 EN ETOS TD 15 2 2 2 ETOS TD L ...
Страница 332: ......
Страница 333: ...15 Technical data Maschinenfabrik Reinhausen GmbH 2020 333 4453918 14 EN ETOS TD 15 2 2 3 ETOS TD XL ...
Страница 334: ......
Страница 355: ......