9 Visualization
Maschinenfabrik Reinhausen GmbH 2020
129
4453918/14 EN
ETOS
®
TD
Figure 93: Status of cooling stages
► Go to
Information > Cooling system > Cooling system control
.
9.11 Cooling system monitoring (optional)
With the optional cooling monitoring function, you can monitor the cooling
system of a transformer.
9.11.1 Setting the cooling system monitoring function
You can set the general cooling system monitoring functions with the follow-
ing parameters.
Settings
Parameters
Cooling sy...ing
Name
Value
Run-in time evaluation
60 s
Operating duration
0 s
Number of starts
0
Operating duration
0 s
Number of starts
0
Home
Events
Information
Recorder
Settings
EN
CHANGE
REBOOT
admin
05.02.2020 10:09
Figure 94: Cooling system monitoring
1. Go to
Settings > Parameters > Cooling system > Cooling system
monitoring
.
2. Select the desired parameter.
3. Set the parameter.