9 Visualization
Maschinenfabrik Reinhausen GmbH 2020
291
4453918/14 EN
ETOS
®
TD
5. In the
Basic settings > Network > Global
menu, adjust the network set-
tings and click on the
Write
button.
Figure 219: Network settings
6. In the
Basic settings > Load/Save
menu, click on the
Save
button to per-
manently store the settings.
7. If necessary, establish a connection to the new IP address to continue
changing settings. Click on the
Help
button to find out more information.
8. Attach the cable for connecting to your network.
9.37.2 Configuration
You can use the web interface to configure the Ethernet switch. You can find
more information about the configuration using the online help in the web in-
terface.
Calling up the web interface
To access the web interface, follow the instructions outlined in the Commis-
sioning [
Section 9.37.1, Page 290] chapter.
Selecting the redundancy protocol
To select the redundancy protocol, proceed as follows:
1. Go to
Redundancy
.
2. Select the specific menu item for the redundancy protocol.
3. Change the configuration and select the
On
option in the
Function
group
field.
4. In the
Basic settings > Load/Save
menu, click on the
Save
button to per-
manently store the settings.
Содержание ETOS TD
Страница 1: ...Motor drive unit ETOS TD Operating Instructions 4453918 14 EN ...
Страница 329: ...15 Technical data Maschinenfabrik Reinhausen GmbH 2020 329 4453918 14 EN ETOS TD 15 2 2 Drawings 15 2 2 1 ETOS TD S ...
Страница 330: ......
Страница 331: ...15 Technical data Maschinenfabrik Reinhausen GmbH 2020 331 4453918 14 EN ETOS TD 15 2 2 2 ETOS TD L ...
Страница 332: ......
Страница 333: ...15 Technical data Maschinenfabrik Reinhausen GmbH 2020 333 4453918 14 EN ETOS TD 15 2 2 3 ETOS TD XL ...
Страница 334: ......
Страница 355: ......