9 Visualization
Maschinenfabrik Reinhausen GmbH 2020
210
4453918/14 EN
ETOS
®
TD
9.22.10 Monitoring the gas volume of the Buchholz relay (OLTC)
When you record the gas volume of the Buchholz relay of the on-load tap-
changer, you can set 2 limit values for the gas volume. If the on-load tap-
changer has multiple columns, you can set 2 limit values for each column. If
the measured gas volume is greater than the limit value > or >>, the device
triggers an event message.
Settings
Parameters
Buchholz relay
>
OLTC gas volume
0.3 l
0.4 l
Home
Events
Information
Recorder
Settings
EN
CHANGE
REBOOT
admin
04.02.2020 11:14
Figure 142: Limit values for the gas volume of the Buchholz relay of the on-load tap-changer
1. Go to
Settings > Parameters > On-load tap-changer > Buchholz relay
.
2. Select the desired parameter.
3. Set the desired parameter.
4. Press the
Accept
button to save the modified parameter.