9 Visualization
Maschinenfabrik Reinhausen GmbH 2020
219
4453918/14 EN
ETOS
®
TD
Note that, for measured values via analog input signals (e.g. temperature),
a maximum of 100,000 measured values with an average value interval of
3,600 s (= 1 h) will be saved. This is equivalent to a time period of approx.
11 years.
Settings
Parameters
Recorder
Name
Value
Mean value interval
360 s
Home
Events
Information
Recorder
Settings
EN
CHANGE
REBOOT
admin
04.02.2020 11:14
Figure 151: Recorder
1. Go to
Settings > Parameters > System > Recorder
.
2. Select the desired parameter.
3. Set the parameter.
4. Press the
Accept
button to save the modified parameter.
Average value interval
You can use this parameter to set the average value interval of the mea-
sured value recorder for electrical measured variables (current, voltage,
phase angle etc.).