voltage regulators as a correction for the control deviation determined on the
basis of the measurement voltage. You can use the circulating reactive cur-
rent sensitivity parameter to decrease or increase this extra control devia-
tion.
The circulating reactive current method is suited to transformers connected
in parallel with a similar nominal output and short-circuit voltage U
K
and to
vector groups with the same and different step voltages. This does not re-
quire any information about the tap position.
Note that the following prerequisites must be met for the "circulating reactive
current minimization" parallel operation method:
▪ You have to use current transformers with the same rated values for all
transformers in parallel operation.
▪ If you wish to operate in parallel operation with existing devices, you have
to activate the Retrofit TAPCON® 2xx [
rameter.
For the circulating reactive current minimization parallel operation method
with CAN communication, you have to set the following parameters:
▪ Activate parallel operation
▪ Parallel operation method: Circulating reactive current
▪ CAN bus address
▪ Circulating reactive current sensitivity
▪ Circul. reactive current blocking limit
▪ Error if no communication present
▪ Behavior if no communication present
▪ Parallel operation error delay time
Содержание ETOS TD
Страница 1: ...Motor drive unit ETOS TD Operating Instructions 4453918 14 EN ...
Страница 329: ...15 Technical data Maschinenfabrik Reinhausen GmbH 2020 329 4453918 14 EN ETOS TD 15 2 2 Drawings 15 2 2 1 ETOS TD S ...
Страница 330: ......
Страница 331: ...15 Technical data Maschinenfabrik Reinhausen GmbH 2020 331 4453918 14 EN ETOS TD 15 2 2 2 ETOS TD L ...
Страница 332: ......
Страница 333: ...15 Technical data Maschinenfabrik Reinhausen GmbH 2020 333 4453918 14 EN ETOS TD 15 2 2 3 ETOS TD XL ...
Страница 334: ......
Страница 355: ......