9 Visualization
Maschinenfabrik Reinhausen GmbH 2020
226
4453918/14 EN
ETOS
®
TD
The motor runtime and therefore the Motor Current Index differ depending
on the type of tap-change operation. The Motor Current Index will therefore
be categorized in accordance with the following types of tap-change opera-
tion to aid comparison:
Tap-change operation type
Description
Tap selector operation / change-
over selector operation
The switching direction is the same as the pre-
vious switching direction. Example:
▪ Previous tap-change operation: pos. 2 →
pos. 3
▪ Current tap-change operation: pos. 3 →
pos. 4
Reverse tap-change operation
The switching direction is not the same as the
previous switching direction. Example:
▪ Previous tap-change operation: pos. 2 →
pos. 3
▪ Current tap-change operation: pos. 3 →
pos. 2
Unknown
The tap-change operation type is unknown.
This is the case after the device has been
restarted or if the motor protective switch has
been triggered.
Table 75: Tap-change operation types
For the correct determination of the Motor Current Index, you must use a
signaling module for the tap position that also signals the pass-through posi-
tion as a separate tap position.
Содержание ETOS TD
Страница 1: ...Motor drive unit ETOS TD Operating Instructions 4453918 14 EN ...
Страница 329: ...15 Technical data Maschinenfabrik Reinhausen GmbH 2020 329 4453918 14 EN ETOS TD 15 2 2 Drawings 15 2 2 1 ETOS TD S ...
Страница 330: ......
Страница 331: ...15 Technical data Maschinenfabrik Reinhausen GmbH 2020 331 4453918 14 EN ETOS TD 15 2 2 2 ETOS TD L ...
Страница 332: ......
Страница 333: ...15 Technical data Maschinenfabrik Reinhausen GmbH 2020 333 4453918 14 EN ETOS TD 15 2 2 3 ETOS TD XL ...
Страница 334: ......
Страница 355: ......