1. Go to
Settings > Parameters > Cooling system > Cooling efficiency
monitoring
.
2. Select the desired parameter.
3. Set the parameter.
4. Press the
Accept
button to save the modified parameter.
Transformer short-circuit losses
You can use this parameter to set the transformer short-circuit losses (cop-
per losses)
P
CU
for calculating the thermal resistance of the cooling system.
Transformer no-load losses
You can use this parameter to set the transformer no-load losses
P
0
for cal-
culating the thermal resistance of the cooling system.
9.11.2.2 Displaying the cooling efficiency
You can display the temporal progression of the average value of the ther-
mal resistance
R
th
of the cooling system over the last 10 days.
Figure 96: Cooling efficiency
► Go to
Information > Cooling system > Cooling efficiency
.
9.11.3 Cooling system flow monitoring (optional)
The device can monitor a cooling system with 2 oil-water cooling stages. To
do this, the device monitors the following values for the cooling media oil and
water:
▪ Temperature
– Feed
– Return
– Difference feed/return (oil only)
Содержание ETOS TD
Страница 1: ...Motor drive unit ETOS TD Operating Instructions 4453918 14 EN ...
Страница 329: ...15 Technical data Maschinenfabrik Reinhausen GmbH 2020 329 4453918 14 EN ETOS TD 15 2 2 Drawings 15 2 2 1 ETOS TD S ...
Страница 330: ......
Страница 331: ...15 Technical data Maschinenfabrik Reinhausen GmbH 2020 331 4453918 14 EN ETOS TD 15 2 2 2 ETOS TD L ...
Страница 332: ......
Страница 333: ...15 Technical data Maschinenfabrik Reinhausen GmbH 2020 333 4453918 14 EN ETOS TD 15 2 2 3 ETOS TD XL ...
Страница 334: ......
Страница 355: ......