No ignition sensor unit is required for the ASO output
If you use a MOTORTECH ignition controller (e. g. MIC6) with auxiliary
synchronization output (ASO), you do not need any ignition sensor unit
(ISU). In this case, the ignition pulse is transmitted to the DetCon via the
ASO output.
Overview of Use: Ignition Sensor Unit and Load Resistance Jumper
The following table provides an overview of the applications for which you
must use the ignition sensor unit (ISU) and when the jumper
Load
Resistance
on the DetCon device must be removed:
Pilot injection
or diesel engine
Gas
engines
Without ASO
output (e. g.
MIC500)
With ASO output
(e. g. MIC850,
MIC6)
Ignition sen-
sor unit (ISU)
required
No
Yes
No
Jumper
Load
Resistance
Remove jumper
Jumper set
Remove jumper