2 User Control Levels
2.1 Level Definition
•
The ZXa and ZXe Fire Alarm Control Panels have three user control levels.
•
At all three levels, the LED Displays indicate the condition of the installation, the Zone LED Displays indicate the
location of any fire alarm or fault and the alphanumeric display gives more detailed fire alarm or fault information.
•
At USER LEVEL 1, all the displays are functional but the front panel control keys are inhibited.
•
At USER LEVEL 2, all front panel controls are functional and some system operation parameters and functions
can be changed. User Level 2 is reached by entering a password from level 1.
•
At USER LEVEL 3, all front panel controls are functional and full system configuration and programming are
possible. User Level 3 is reached by entering a password from either Level 1 or Level 2. User Level 3 is intended
for use by the system installer / maintenance contractor.
2.2 User Passwords
•
Up to ten USER LEVEL 2 passwords can be programmed into the panel.
•
The USER LEVEL 2 passwords can be assigned / changed at Level 3 by the installer / maintenance contractor.
Level 2 passwords do not allow access to Level 3 functions.
The Default Level 2 password is 1234. At initialization, only one Level 2 password is enabled.
The Level 3 password is ####. This password cannot be changed. To ensure panel security,
do not set a Level 2 password to be the same as the Level 3 password.