ZX
A
/ Z
XE
MORLEY-IAS
C
OMMISSIONING
M
ANUAL
Document No. 996-071, Revision:
1
,
Aug 99
Page
41
Network Option
Option setting
Comments
Panel network-address
number
1..20
Enter Master’s own address, i.e. 4.
Quantity of slave
processors
1..20
Number of slaves DIRECTLY connected to the Master, i.e.
via port C.
Slave CPU 1 is at
network addess
1..20
The address of the first slave panel.
Slave CPU 2 is at
network addess
1..20
The address of the second slave panel.
Etc.
Use modem
[TRUE]/[FALSE]
Set to TRUE if a modem is connected to port C.
Share zones
[TRUE ]
Zones are shared between panels
Peer-to-Peer
[TRUE]
Allow MUTE / ACCEPT, SILENCE / RESOUND and RESET
key presses from a slave panel.
*Port B Protocol
0
Use default of 0 unless special applications interface.
System events
[GLOBAL]/[LOCAL ]
Global -
1.
passes system events over network
2.
accepts other network events
Local -
1.
does not pass events over the network.
2.
ignores other network events
NOTE: The zonal fire status is passed over a shared-zone
network regardless of events being global or local.
Table 10 - Master Panel Network Settings
13.2 Port B Protocols
NOTE: * Port B Protocol is not available on ZXa panels.
•
The Port B serial interface supports a number of different protocols.
•
These can be used to define the connections as:
1. Standard MORLEY-IAS Panel Network / Graphics PC Interface
2. Pager Interface
3. Other PC System Interface
•
The following table defines the settings to be entered for each interface type.