MORLEY-IAS
ZXa / Zxe
C
OMMISSIONING
M
ANUAL
Page
14
Document No.996-071, Revision:
1
,
Aug 99
All devices on Loop 01 from address
[024] to address [126] are in zone [01]
•
The
">"
&
"<"
keys can be used to move across the display. For example, if the ‘126’ in the "to address" field is
flashing, then the ‘zone’ field can be modified by pressing the
">"
key to make the zone number flash and then
entering the desired value.
•
The backspace
"<"
key also moves back one digit - useful for correcting errors when entering numbers.
•
The configuration shown on the display becomes effective immediately after the "
Enter
" or "
Yes
" key is pressed.
Pressing the "
No
" key will abort the operation and return to the commissioning menu.
•
If the "to address" value is less than 126, the "
Yes
" or "
Enter
" key automatically advances to the next zone to be
defined.
•
When all of the devices for the loop being configured are assigned to zones, then the program will advance to the
zone description - text entry menu.
•
Each zone can have a description assigned to it to identify the area covered by the zone. This description will
appear on the liquid crystal display if a fault or fire is detected by any sensor in the zone.
Zone 01 is named = “SOUTH ANNEXE “
•
The description can be amended by highlighting the location text (using the
‘>‘
and
‘<‘
keys), pressing "
Change
"
and entering either, letters, numbers or keywords. This procedure is identical to that used for editing the sensor
location text described in section 5.2.3.2 below.
5.2.3 Devices
•
The "Devices" option from the display gives information on the various types of device fitted on a loop.
•
Press 2 to select the "Devices" option. The system will ask which address you want to start at :-
Begin inspection at address number 1 ?
•
If you would like to start at a different address, then press the "
Change
" key and enter your required address,
otherwise say "
Yes
" to continue.
•
The display then gives detailed information about the Device at the chosen address.
L1 Z003 A086 RESEARCH ROOM 52 “ Ev106
Ion Smoke Signal= 26 (Inputs 2..0=LLH)
Loop Zone Address
Location Text
Event
Device Type
Analogue Signal
Digital input status (Apollo only)
H=Logic High L=Logic Low