MORLEY-IAS
ZXa / Zxe
C
OMMISSIONING
M
ANUAL
Page
48
Document No.996-071, Revision:
1
,
Aug 99
16.3.5 Disablement of addressable points:
•
The control panel has the facility to disable / enable signals from addressable points at User Level 2, either
individually or by complete zones.
•
Each device disabled in this manner is identified at User Level 1 and zone disablement’s are only indicated as
such, when all devices within that zone are disabled.
16.3.6 Test condition :
•
A test facility exists, in which the user, at User Level 2, can test the operation of fire alarm detectors. When
testing the fire alarm system in this manner, the following conditions apply:
1. The control panel is in a test condition and indicates such, when one or more zones are in test.
2. The test mode can only be entered or canceled by manual operation at User Levels 2 or 3
3. It is possible to test the operation of each zone on an individual basis.
4. Zones in a test state do not prevent the mandatory indications or outputs from zones, which are not in a
test state.
5. Signals from a zone under test do not lead to the operation of outputs to fire alarm devices, except for
short periods, during which the devices function can be tested in relation to the zone under test.
16.4 Printer Set-Up Options
•
The Printer ‘Set-up’ allows the panel to be configured for the type of printer connected.
•
A Level 3 password must be entered before access to the printer set-up function is given.
•
Refer to the FACP User Manual for further information on the use and operation of the printer.
•
The default printer type code (2) is displayed on the printer set-up screen. To change the value, either press NO
or CHANGE and then enter the required number.
•
The following table lists the settings for each available printer type.
Model
Part Number
Description
Setting
EXP-051
795-051
Compact Internal 1200 bps ink-ribbon printer (ZXe)
2
EXP-055
795-055
PC Print Capture Software
2
EXP-060
795-060-xxx
Boxed Local / Remote 9600 bps thermal printer
3
•
The Local or Remote Boxed Printer (Type 3) provides additional options to selectively print only certain types of
message. Refer to the Installation Instructions supplied with the printer for further information.