Document No.996-071, Revision:
1
,
Aug 99
12 Setup Option
•
Setup options define the way in which the panel is configured, such as the number and type of loop driver boards
fitted. They should be checked when a panel is first installed, but will rarely need altering after this time.
•
The options are presented as a series of questions. Press
Yes
if the setting is as required. The following table
details the options:
Option
Description
Default
Language
Determines the language displayed on the alphanumeric display.
Options: Language options depend on the software version installed.
If only one language available, this option is not displayed.
English UK
No of Loop Drivers
Determines the number of loop driver boards installed in the panel.
(ZXa = 1 to 2, ZXe = 1 to 5).
--
Type of Loop Driver
Determines the type of loop driver installed. Options: System Sensor,
Apollo, Hochiki ESP, Nittan
.
NOTE: Isynch compatible, loop driver boards self identify and do not
need to be changed manually. The Isynch software installed in the
board is also displayed on the bottom line.
--
Approvals Standard
Determines the standard to which the panel software complies.
Options: UL864, EN54.
EN54
Calibration Time
Determines whether calibration should be performed on the detectors.
Automatic checking of device calibration can be performed at the time
specified. A warning will be given if a device drifts outside its calibration
limits or approaches the pre-alarm threshold. Setting a time of 0:00 will
prevent this check from taking place. Choose a time of day when the
environment can be expected to be in a normal condition.
00:00
Device Interrupts
Device interrupts provide a way for call point devices to interrupt the
normal polling sequence and so give a fast response. It is possible to
ignore interrupts, if required, by changing this item to “False” instead of
the default “true” setting.
This option should normally be set to True unless faultfinding on a
system during the early commissioning phase.
Hochiki ESP devices rely on interrupts for their basic operation and so
do not display this option.
For System Sensor (SSD) devices, this option should be set to
FALSE.
TRUE
AC Fail Timer
As soon as the ac power is lost, the panel will flash the green power
supply indicator on the front panel.
The panel will not latch a fault condition, until the AC Fail Timer has
elapsed.
The AC Fail Timer can be set in the range 1 – 720 minutes in one-
minute intervals.
1 minute
Reset Inhibit Time
The reset key can be inhibited for a period after the receipt of a fire
alarm condition at the panel.
The Reset Inhibit Time can be set in the range 0 – 900 seconds in one-
second intervals.
0 seconds
Silence Inhibit Time
The Silence / Resound key can be inhibited for a period after the panel
receives a fire alarm condition.
The Silence Inhibit Time can be set in the range 0 – 900 seconds in
one-second intervals.
This option is only shown if the Reset Inhibit Time is not equal to zero.
If the Reset Inhibit Time is set to zero, this function is made inactive
.
0 seconds