5.2.3.1 Changing Device Information
•
Changes are made by first pressing the "
Change
" key. A menu of items that can be changed will appear
according to the type of device, For example.
•
An ionization smoke detector will allow changes on :-
1)Sensor Text 2)Zone 3)Event
4)Alarm thresholds 7)Group
•
A call-point will allow changes on :-
1)Sensor Text 2)Zone 3)Event
6)Action 7)Group
•
Press the appropriate
number
to select the required option. Press ‘
No’
to return to the device information display.
•
NOTE: This change facility is only available while in the configure mode. It cannot be invoked from the INSPECT
option, thus preventing inadvertent changes to the system.
5.2.3.2 Location Text
•
To enter or modify the location text assigned to a device, press
1
to select the "Sensor Text" option. The display
will show the current location text and provide additional information to assist in making any changes.
•
Three modes of text entry are available - "KeyWords", "Numbers" and "Letters". The mode currently in use is
always shown in square brackets in the top right hand corner of the display. The required mode is selected by
pressing either the
Yes
(Keyword) button or the
No
(Letters/Numbers) button.
Text = “FLOOR 2 ROOM 86_ “ [Numbers ]
Type in number 0..9
A) Numbers
•
The number mode allows you to add numbers 0 to 9 on the display.
•
Advance and Backspace editing keys are also available in this mode.
•
For example, to change from "ROOM 86" to "ROOM 87", first press the backspace key once to erase the "
6
",
then press key “
7
”. The display will immediately show the new description as below :-
Text = “FLOOR 2 ROOM 87_ “ [Numbers ]
Type in number 0..9
•
The cursor symbol "_", indicates where you are on the line. It will not appear in the description shown on the
device display.