MORLEY-IAS
ZXa / Zxe
C
OMMISSIONING
M
ANUAL
Page
12
Document No.996-071, Revision:
1
,
Aug 99
5 Configure Option
5.1 Accessing the Configure Option
•
Page 1 of the Commission menu is shown below:
1)CONFIGURE YES)More Options [1]
2)Inspect 3)NORMAL OPERATION
•
The CONFIGURE option allows the Signaling Loops, peripherals, sounders and relays to be programmed. It also
enables the function to allow the panel to be programmed by a PC.
•
Press 1 to select the CONFIGURE option.
The CONFIGURE option and all sub menu options require the Memory Lock to be open.
•
The display then shows a menu of options as follows:
CONFIGURE : Loop 1) 2) 3) 4) 5) [1]
6)Peripherals 7) Sounders 8)Relays 9)PC
•
NOTE: The menu will only show the number of signaling loops programmed during setup (Refer to the Setup
Option. The ZXa can only have two loops maximum.
5.2 Signaling Loops
•
After selecting a loop from the configure menu, the display will present a list of options as follows:
CONFIGURE : Loop 1) 1)Zones [1]
2)Devices 3)Auto Learn 4)Calibrate
The top left-hand corner of the display provides a reminder that panel is in configure mode
with loop 1 selected.
•
Select the required option by pressing the appropriate numeric key.
•
When commissioning a new panel, start by performing an “Auto Learn”. This will cause the panel to search for all
devices installed on the loop.