ZX
A
/ Z
XE
MORLEY-IAS
C
OMMISSIONING
M
ANUAL
Document No. 996-071, Revision:
1
,
Aug 99
Page
19
1. Fault warning
Closing the input produces a “warning” message on the display. The
common “Fault” LED and the corresponding zone fault LED will also
illuminate.
2. Zone Fire
Closing the input puts the designated zone into fire. “True” Break Glass Call
Points should
ALWAYS
be set to this option.
3. Bomb Alert
Creates a "bomb alert" from the designated zone. All sounders / relay
outputs will react according to their programming for this zone.
4. Class Change
Closing the input forces all on-board sounders to ring. This condition is not
latched. Once the input opens again the sounders will stop ringing.
5. Security
Creates a security alert.
6. Non-latching
Allows an input device to create a temporary system event that is cleared
when the input is restored to it's normal condition. This option is not
normally used on fire systems. Contact applications department for further
information before using this option.
7. Plant warning
Closing the input produces a “warning” message on the LCD, but does not
illuminate the yellow fault LED’s.
8. Group Disable
Allows an input device to disable a group of detectors remotely from the
panel.
9. not used
Allows an input device to be turned off. Any action or state change at the
input will be ignored.
Table 6 - List of Device Actions
•
Press the
Yes
key once the desired option is shown. The display will then revert to the normal device display, but
will in addition show in the bottom right corner the alarm action of the input. For example:
L1 Z056 A106 “PLANT CONTROL ROOM “
I/O unit Signal= 16 Security
•
The display can also be placed in this “action display” mode at any time by pressing the “
6
” key when viewing any
device.