ZX
A
/ Z
XE
MORLEY-IAS
C
OMMISSIONING
M
ANUAL
Document No. 996-071, Revision:
1
,
Aug 99
Page
45
14.1.3 Define Event Outputs
•
All output devices can have two system events directly assigned to them.
•
A relay style device will turn on if either of the assigned events occur.
•
A sounder style device will turn on if the primary event occurs, (Shown as “Event-A”), or will pulse if only the
secondary event occurs (“Shown as Event-B”).
•
The “Define outputs” display option allows the events assignments to be inspected and changed if required.
It strongly recommended that a PC be normally used to define events.
•
Press the “No” key to terminate this display option.
15 Normal Operation
•
The panel is placed in its normal operating state by selecting “NORMAL OPERATION” from Page 1 of the
commissioning menu. Press
3
to select the function.
•
Once this is done the panel will perform a reset and then become fully active. The alphanumeric display may
prompt for entry of the time and date – enter the correct time and date as appropriate.
•
Refer to the User Manual for further information on the operation and functions available at User Levels 1 and 2.
Remember to lock the memory.