1)Time/Date 2)Program Integrity [1]
3)Power Supplies 4)Passwords
PAGE 3
1)Day Modes 2)Setup Options 3)Network [1]
4)Events
Page
Option
Function
Configure
To configure the connection and operation of the signaling loop devices, peripheral
devices, sounder circuits and relay outputs.
Also provides configuration for upload / download of configuration data from a PC.
Inspect
Provides the same functionality as the configure option but with view only. This allows
the data to be inspected without risking any inadvertent changes.
1
Normal Operation
To return the panel to normal operation – Level 2.
Time / Date
To allow the date and time and other clock functions to be changed.
Also allows the system memory to be cleared to return the panel back to factory
default settings.
Program Integrity
To show the version of the software installed in the panel.
To show the status of the operating program and configuration memory.
Power Supplies
Shows the current state of the AC Mains and Battery supply conditions.
NOTE: Should the AC Mains fail, the back lighting on the liquid crystal display will be
turned off to conserve battery power.
2
Passwords
To define the number of User Level 2 passwords.
To define the value of each Level 2 password.
To define the maximum time the panel will remain at Level 2, without any key pressed,
before inhibiting the keys and returning to Level 1 operation.
Day Modes
To define which, if any, of the following day modes are in operation.
1.
Delayed Mode
2.
Sensitivity Mode
3.
Verification Mode
To define the effective times of operation, (i.e. start and finish).
Setup Options
To define system setup parameters.
Network
To define and configure the operation of the panel in a networked system.
3
Events
To define system events that provide a more flexible cause and event function than
that available from standard zone based ringing options.
Table 4 - Menu Funtion Overview