11.2 Delayed Mode
•
The panel can be configured to operate in a delayed mode during the daytime in any specified zone.
•
During this time, high sensor signals will generate a fire message at the panel, but delay the output to the
sounders. The panel will initiate a full fire alarm if action is not taken on this warning within a specified time.
•
Manual call points (Pull Stations) will always generate an immediate fire alarm, regardless of any day mode
setting.
11.2.1 Commissioning Delayed Mode
•
Press
1
to select Delayed mode from the ‘Day Modes Menu. The display will prompt whether the mode is to be
used.
Allow mode ?
•
Press
No
to inhibit the mode and return to the ‘Day Mode’ menu.
•
Press Yes to enable the mode. The display will then prompt the start and end times for the day period.
START at 08:45 ?
•
Press
Yes
to accept and step on. Press
No
to change and then enter the required start time using the number
buttons.
START at 08:45 FINISH at 16:35 ?
•
Press
Yes
to accept and step on. Press
No
to change and then enter the required end time using the number
buttons.
•
A two stage timer is built into the day mode.
•
After entry of the start / end times, the display prompts the stage timers as follows:
Stage 1 time = 30 seconds OK ?
•
Press
Yes
to accept and step on. Press
No
to change and then enter the required end time using the number
buttons.
Stage 2 time = 120 seconds OK ?